Hopper Configuration#
Problem |
Possible Causes |
Solutions |
|---|---|---|
Control area cannot be defined |
• Image not acquired • Wrong section |
• Acquire test image • Access through Config Hopper X |
AUTO does not calculate Mean and Std Dev correctly |
• CAPTURE not performed • CAPTURE order reversed • Control area too small |
• Perform empty CAPTURE then full CAPTURE • Repeat in the correct order • Enlarge the control area |
TEST always GREEN (hopper never activates) |
• Threshold too permissive • Full CAPTURE with too many components • Incorrect calculated Mean |
• Repeat full CAPTURE with the correct minimum number • Verify that AUTO recalculates correctly • Manually adjust the threshold if necessary |
TEST always RED (hopper always activates) |
• Threshold too restrictive • Empty CAPTURE with components present |
• Repeat empty CAPTURE with a completely clean area • Repeat AUTO |
Vibration time does not produce the desired effect |
• Value too low • Value too high • Variable hopper bowl level |
• Start with 500ms • Increase by ±100ms to adjust the flow • CRITICAL: Maintain a constant load in the bowl |
Hopper discharges at the wrong times |
• Incorrect Steps • Hopper Controller hardware not configured correctly |
• Recalculate Steps • Check the configuration specifications in the dedicated Hopper manual |