FlexiBowl Wizard#
Problem |
Possible Causes |
Solutions |
|---|---|---|
Wizard does not start |
• Recipe not loaded • FlexiBowl not connected • Initial setup not completed |
• Load or create a recipe first • Check FlexiBowl connection • Complete basic system configuration |
Set rotation direction does not match |
• CW/CCW selection error |
• Visually verify the actual rotation direction • Correct the selection in the Wizard |
Air-blow test does not work |
• Compressed air not connected • Insufficient pressure • Module not physically present |
• Check compressed-air connection • Increase pressure to 5-6 bar • Select “FlexiBowl NOT equipped” if the module is absent |
Flip test not noticeable |
• Compressed air not connected/insufficient • Pressure regulator closed • Pneumatic circuit leaks |
• Verify compressed air is connected • Open regulator on control panel • Verify pressure 5-6 bar • Inspect fittings for leaks |
Calculated parameters not optimal |
• Incorrect component characterization • Wizard uses generic values |
• Review selected geometry and behavior • Accept Wizard parameters as a starting point • Fine-tune manually in the summary dashboard |
Components move during acquisition |
• Speed/acceleration too high • Stabilization pauses absent • Grip surface not suitable |
• Decrease Speed and Accel • Insert 200-500ms pauses • Replace grip surface with a more adhesive one |
Air blow not effective |
• Air pressure insufficient/excessive • Nozzles clogged |
• Verify pressure 5-6 bar • Clean air-blow nozzles |
Parameter changes are not applied |
• “Synchronize Parameters” not pressed • Recipe not saved |
• ALWAYS click Synchronize Parameters after changes • Save recipe to make changes permanent |
Turn FLB does not work during setup |
• FlexiBowl not connected • Command not configured • FlexiBowl in error |
• Check FlexiBowl connection • Check FlexiBowl Setup configuration • Check FlexiBowl READY LED |